Minimum Sump Dimensions (in accordance with BS EN 12845)
Diameter (D)
Deadwater
Level
(mm)
Minimum Sump Dimensions (mm)
Pipework
Length
(mm) (C)
Length (L)
Width (W)
Depth (A)
100NB
30
1000
600
170
1050
150NB
30
1375
900
170
1150
200NB
30
1750
1200
220
1250
250NB
30
2125
1500
270
1350
300NB
30
2500
1800
270
1450
350NB
30
2775
2100
370
1450
400NB
30
3050
2400
370
1450
450NB
30
3325
2700
420
1450
Sump offset from tank shell = 600mm